• JDZX10-3、6、10(A、B) Single phase hermetically casted semi-insulation voltage transformer
  • JDZX10-3、6、10(A、B) Single phase hermetically casted semi-insulation voltage transformer
  • JDZX10-3、6、10(A、B) Single phase hermetically casted semi-insulation voltage transformer
  • JDZX10-3、6、10(A、B) Single phase hermetically casted semi-insulation voltage transformer

JDZX10-3、6、10(A、B) Single phase hermetically casted semi-insulation voltage transformer

The JDZX10-3/6/10 (A, B) is a single-phase, hermetically casted semi-insulated voltage transformer designed for medium-voltage systems up to 3kV, 6kV, and 10kV. It adopts high-quality epoxy resin casting, offering excellent insulation performance, compact structure, and reliable operation.
  • JDZX10-3、6、10(A、B) Single phase hermetically casted semi-insulation voltage transformer
  • JDZX10-3、6、10(A、B) Single phase hermetically casted semi-insulation voltage transformer

Description

Description
Pouring the closed structure of semi-insulating voltage transformer of this type for the epoxy resin, for rated frequency 50-60Hz Rated voltage for voltage 3,6,10 kv exchange of indoor installations, energy measurement, or relay, the products are characterized by small size, light weight, can be installed in any direction.

Characteristic of structure
This type of votae transformer s fuly enlosed structure. Core using superior grade quaity cold rolled silicon steel around the system, and strict heat treatment, the core and arimary winding with epoy resin and the secondary winding of advanced vacum casting process casting, transformer resitant fithy. resitant to molsture performancebeter. Secondary outlet terminal outlet terminal box. The terminal box has thre diferent outlet directions and easy to wire. And to achieve the anti tamper measures.

Applications
1.Switchgear
2.Power Distribution Systems
3.Industrial Power Systems
4.Energy Metering Systems
5.Protection Systems

 Technical Data
Product standard: Gb1207
Pollution class: class Il
Load power factor: COSΦ = 0.8 (lag)
Other technical parameters are as follows
Type Rated voltage ratio(kV) Rated output(VA) limit output(VA) Reted insulating level(kV) Remark
0.2 0.5 1 6P
JDZX10-3A 3/√3/0.1/√3/0.1/3 15 30 60 50 150 3.6/25/40 With REL
JDZX10-6A 6/√3/0.1/√3/0.1/3 7.2/30/60
JDZX10-10A 10/√3/0.1/√3/0.1/3 12/42/75
JDZX10-3B 3/√3/0.1/√3/0.1/3 20 50 90 400 3.6/25/40
JDZX10-6B 6/√3/0.1/√3/0.1/3 7.2/30/60
JDZX10-10B 10/√3/0.1/√3/0.1/3 12/42/75