LB6-110(W2)、LB6-110GYW2 Oil-immersed type current transformer

This series of instrument transformers is designed for use in 50 Hz, 110 kV power systems for current and energy metering, as well as for relay protection purposes.
Featuring a fully sealed structure equipped with a metal expansion device, this product series utilizes a "U"-shaped capacitive insulation structure for its primary winding. This design ensures a uniform electric field distribution, low dielectric loss, and minimal partial discharge levels. The secondary side typically comprises 3 to 6 windings, the configurations of which can be freely combined. Furthermore, upon user request, specialized current transformers with a metering accuracy class of 0.2s can be manufactured for specific applications.
This product series is designed for outdoor installation and operates within an ambient temperature range of -30°C to +40°C.
  • LB6-110(W2)、LB6-110GYW2 Oil-immersed type current transformer

Description

Introduction
This series of instrument transformers is designed for use in 50 Hz, 110 kV power systems for current and energy metering, as well as for relay protection applications.

Featuring a fully sealed structure equipped with a metal expansion device, this product series utilizes a "U"-shaped capacitive insulation structure for its primary winding. This design ensures a uniform electric field distribution, resulting in low dielectric loss and minimal partial discharge levels. The secondary windings typically consist of 3 to 6 coils, the grades of which can be freely combined. Furthermore, upon user request, we can manufacture specialized current transformers—including those with a measurement accuracy class of 0.2s—tailored to specific application requirements.

Structural Features
The transformer adopts an oil-immersed insulation structure with a fully sealed design, ensuring excellent dielectric performance and effective heat dissipation. Its stable internal structure provides high measurement accuracy, while strong resistance to environmental factors such as moisture, pollution, and temperature variations guarantees reliable long-term outdoor operation.

Applications
1.110kV high-voltage substations

2.Power transmission and distribution systems
3.Grid monitoring and automation systems
4.Outdoor installations in harsh environments

Technical Data

Rated
Voltage(kV)
Rated
primary
current(A)
Class combination Ratedprimany current(A) Accuracy
class
Rated output Accuracy Limit tactor Rated short-time themal current(kA) dynamic
stable
current(kA)
Rated
insulation level(kA)
Specific creepage distance(cm/kv) oil weight(kg) Total weight(kg)
Full turn
number
Tap
110 2x50 P/P/0.5(0.2)
P/0.5/0.2
P/P/0.2S
P/P/P/0.5(0.2)
P/P/0.5/0.2
P/P/P/0.2S
P/P0.5/0.2S
P/P/P/P/0.5(0.2)
P/P/P/P/0.2S
P/P/P0.5/0.2S
P/P/P0.5/0.25
P/P/P/P/P/0.5(0.2)
P/P/P/P0.5/0.2S
P/P/P/P/P/0.2S
P/P/P/P/0.5/0.2


5or1 5P10P 50(30) ≥15 5.3-10.6 13-26 126/185/450 1.6 150
(173)
650
(850)
2x75 7.9-15.8 20-40
2x100 0.5 50(30) 10,5-21 27-54
2x150 15.8-31.6 40-80
2x200 0.2 50(30) 21-42 54-108 2.0
2x300 31.5-45 80-15
2x400 0.2S 40(30) 45 115
2x500 45 115 2.5